Features
Integrated UV/IR dual-sensor
Detects hydrocarbon-based fuel and gas fires
Response time: 3 seconds, typically
Sample detection ranges (at highest sensitivity setting for 1 ft2 pan fire):
Gasoline: 66 feet
Diesel fuel: 50 feet
Methane: 39 feet
Field of view: Horizontal 100˚; Vertical 95˚
Solar blind to help eliminate false alarms
Automatic and manual Built-In-Test to ensure continued reliable operation
Heated optics eliminates condensation and icing on the window for operation in harsh weather
User programmable via HART® or RS-485
Spectral response:
UV: 0.185–0.260 μm
IR: 4.4–4.6 μm
Meets MIL-STD-810C for Humidity, Salt & Fog, Vibration, Mechanical Shock, High Temp, Low Temp
Approved to Safety Integrity Level 2 (SIL 2 – TÜV)
IP66 and IP67 rated per EN 60529, NEMA 250 6P
Meets NFPA Regulatory Standards
Hazardous area approvals: ATEX and IECEx, FM and CSA