Description
Features
Multi-spectrum design for long-distance detection of fuel and gas fires
High false alarm immunity
4 sensitivity ranges ensures no zone crossover detection
Sample detection ranges (at highest sensitivity setting for 1 ft2 pan fire):
Gasoline: 215 feet
Diesel fuel: 150 feet
Methane: 150 feet
Field of view: Horizontal 100˚; Vertical 95˚
Response time: typically 5 seconds
Automatic and Manual Built-In-Test (BIT) to ensure continued reliable operation
Heated optics eliminates condensation and icing on the window for operation in harsh weather conditions
User programmable via HART® or RS-485
Meets MIL-STD-810C for Humidity, Salt and fog, Vibration, Mechanical Shock, High Temp, Low Temp
Meets NFPA Regulatory Standards
IP66 and IP67 rated per EN 60529, NEMA 250 6P
Hazardous area approvals: ATEX and IECEx, FM and CSA